AC/DC High VoltageTest Systems
Baur PGK50 (50 kV DC)
Baur
PGK50 (50 kV DC)
1
The portable, one-piece PGK50 high-voltage test device for generating negative DC voltage up to 50 kV is primarily used for onsite testing of paper-insulated mass-impregnated cables in the medium-voltage network. The high voltage is generated through a high-voltage transformer with secondary voltage-multiplier. The internal operating frequency of 20 kHz enables the smallest of device dimensions.

Standard set: HV testing device, HV connection cable 4 m., earth cable 3 m., operational earthing cable for current measurement, mains supply cord, user manual, calibration certificate
Price
Add to Cart
Compare Added
Copy
Main features
AC test voltage range
No
AC current output (short-circuit)
No
DC test voltage

+

DC test voltage range
0 ... 50 kV
DC output current (Short-circuit)
25 mA
Leakage current measurement

+

Built-in timer

+

Timer range
0 ... 30 min
Max. power consumtion
1600 VA
Mains voltage 230V, 50Hz

+

Additional features
Weight of control unit
25 kg
Weight of HV unit
One-piece
Operating temperature
0 ... 45 °C
Thermal overcurrent switch-off

+

Special accessories
Discharge and earth rod
411-560
Add to Cart
Compare Added
Copy

All products, product specifications and data present in this website are subject to change without notice.